V-81CONTROL SYSTEMSEnter the received authorization key.Ô Basic optionTemperature display(Celsius and Fahrenheit)Select the outdoor unit type.(Keep the default setting)3) Installation(1) Overview• Before installing S-NET II Plus program, carry out a virus inspection in the PC.• Program installation• Programs to be installed in the PC during program Installation➔ Microsoft .Net Framework 1.1(2) S-NET II Plus authorization process• S-NET II Plus requires an authorization process via normal purchase.With no authorization process, an authorization request pop-up window will be activated when theprogram starts for 7 days. And after 7 days it becomes impossible to use the program. Thus, it is necessaryto enter the proper authorization key.(3) S-NET II Plus option setup• For the first run of the program, select a menu item at the [tool (T)] then [Option(O...)] of the menu itemto open the option window.➔ ON/OFF for the sound effects ofS-NET II Plus programÔ Tracking optionTracking mode selection• Group control : Tracking based on the indoor unit’s RMC address• Room control : Tracking based on the indoor unit’s Main addressSet comm. port connected with the PC.Set the number of tracking retry.Select the user control.• Allow : Permit the use of remote controllers in all indoor units• Deny : Prohibit the use of remote controllers in all indoor units• Allow by Room : Select permission/prohibition of the remote controller for individual indoor units.- Level 1 : Wireless/Wired remote controller is enabled when indoor units areturned on by S-NET II Plus and disabled when they are turned offby S-NET II Plus.05-2_control systems(046~081) 3/6/08 14:02 Page 81