VI-31INSTALLATIONSEG 1 SEG 2, 3, 4Push 1st time Outdoor capacity 1 Ex) 16 HP ➞ Off, 1, 6Push 2nd time Digital comp loading time 2 Ex) Loading 13 sec ➞ Off, 1, 3Push 3nd time High pressure (kg/cm2) 3 Ex) High pressure 15.2 (kg/cm2) ➞ 1, 5, 2Push 4th time Low pressure (kg/cm2) 4 Ex) Low pressure 4.3 (kg/cm2) ➞ 0, 4, 3Push 5th time Discharge temperature of compressor 1 5 Ex) 87˚C ➞ 0, 8, 7Push 6th time Discharge temperature of compressor 2 6 Ex) 87˚C ➞ 0, 8, 7Push 7th time Discharge temperature of compressor 3 7 Ex) 87˚C ➞ 0, 8, 7Push 8th time CT sensor value of compressor 1 8 Ex) 2A ➞ 0, 0, 2Push 9th time CT sensor value of compressor 2 9 Ex) 2A ➞ 0, 0, 2Push 10th time CT sensor value of compressor 3 A Ex) 2A ➞ 0, 0, 2Push 11th time Suction temperature B Ex) -5 ˚C ➞ -, 0, 5Push 12th time Cond_out temperature C Ex) 35 ˚C ➞ 0, 3, 5Push 13th time Liquid tube temperature D Ex) 35 ˚C ➞ 0, 3, 5Push 14thtime Oil temperature sensor on oil balancing pipe E Ex) 35 ˚C ➞ 0, 3, 5Push 15thtime Sump temperature of compressor 1 F Ex) 35˚C ➞ 0, 3, 5Push 16thtime Ambient air temperature G Ex) 35˚C ➞ 0, 3, 5Push 17thtime EVI_in temperature H Ex) 35˚C ➞ 0, 3, 5Push 18thtime EVI_out temperature I Ex) 35˚C ➞ 0, 3, 5Push 19thtime Main EEV1 step J Ex) 2000 steps ➞ 2, 0, 0Push 20thtime Main EEV2 step K Ex) 2000 steps ➞ 2, 0, 0Push 21thtime EVI EEV step L Ex) 300 steps ➞ 3, 0, 0Push 22thtime HR EEV step M Ex) 300 steps ➞ 3, 0, 0Push 23thtime Fan step ( SSR or BLDC ) N Ex) 13 steps ➞ Off, 1, 3Push 24thtime VersionK4 Key function Display LED❈ Note : LED display alphabetSEG 1 SEG 2 SEG 3 SEG 406_Installation(02~45) 3/15/08 4:34 Page 31