Control SystemsV-9633 Integrated management system3-1. DMS (Data Management Server)Setup for power distributionThis setting is mostly used for the case that electricity billing rates differ in time section of day.S-NET3 must be used together to support time section setting for power distribution.Segmented tables for different rate sections are seen on the S-NET3 screen to enter time-dependent billing rates.Environment setup for power distributionThis setting is the most important and attention-requiring task to make reasonable power distribution on the basisthat consumed power in one indoor/outdoor system is distributed to all indoor units in that boundary.Indoor unit addressEx) 00.00.00Watt-hour meter address foroutdoor unit power supplyCentralized controller addressInterface module addressIndoor unit MAIN addressWatt-hour meter address forindoor unit power supply◆ If watt-hour meters are left unmapped to the designated indoor/outdoor units, power distribution is not functioned.But, power distribution ratio is stored and can be used for later power distribution.When watt-hour meters are mapped to the wrong indoor/outdoor units, it also results in incorrect power distribution. Inthis case, it needs bothersome manual calculation to recover correct result.CCCC aaaa uuuu tttt iiii oooo nnnn05-3_control systems(082~141) 3/6/08 14:04 Page 96