73.3 INLETS AND OUTLETSThe standard Monsoon Monitor inlet is CODE-RPF for direct connection to TFT's Extend-A-Gun RC4 (4 inch size). Monitor inlet CODE-RLF is available for direct connection to Extend-A-Gun RC3 (3 inch size). The standard outlet is 3.5”-6 National Hose male. Variousother inlet and outlet adapters are available as shown in figure 3.3A.Fig 3.3AInlets and Outlets3” ANSI 150 (Y4410A)OR4” ANSI 150 (Y4415A)ORDN80 PN16 (Y4423A)ORDN100 PN16 (Y4425A)3” BSP MALE (Y4420A)OR4” BSP MALE (Y4430A)EXTEND-A-GUN RC3OREXTEND-A-GUN RC43” NPT FMALE (Y4440NL)OR4” NPT FEMALE (Y4450NP)CODE-RLFORCODE-RPFINLETMONITOR MOUNTEDCONTROL STATION3.5” BSP MALE (Y4330ABN)3.5” NH MALE (STANDARD)3.5” NPSH MALE (Y4330AIN)4.0” BSP MALE (Y4334ABP)FLANGESIZE3” ANSI 1504” ANSI 150DN80 PN16DN100 PN16OUTSIDEDIAMETER7.50”9.00”200 mm220 mmTHICKNESS.75”.94”22 mm22 mmNUMBEROF BOLTS4888SIZE OFBOLTS5/8”5/8”16 mm16 mmTORQUEON BOLTS76-80 FT-LBS76-80 FT-LBS100-110 NEWTON-METER100-110 NEWTON-METERBOLT HOLECIRCLE6.00”7.50”160 mm180 mm