124 • vacon parameter descriptions99.10 Fieldbus Data-Mapping (Control panel: Menu PAR -> P10)10.1 FB DATA OUT 1 SELECTIONParameter couples read only variables to output process data 1.0 = Frequency reference1 = Output reference2 = Motor speed3 = Motor current4 = Motor voltage5 = Motor torque6 = Motor power7 = DC link voltage8 = Active fault code9 = Analogue AI110 = Analogue AI211 = Digital input state12 = PID feedback value13 = PID setpoint14 = Pulse train / encoder input(%)15 = Pulse train / encoder pulse()10.9 AUX CW DATA IN SELECTIONParameter defines the input process data coupled to Aux Control Word.0 = Not used1 = PDI12 = PDI23 = PDI34 = PDI45 = PDI5