142 • vacon parameter descriptions99.17.3 Modbus process dataProcess data is an address area for fieldbus control. Fieldbus control is active whenthe value of parameter 2.1 (Control place) is 1 (= fieldbus). The content of the processdata can be programmed in the application.The following tables present the processdata contents in Vacon20 Application.ID Modbus register Name Scale Type2101 32101, 42101 FB Status Word - Binary coded2102 32102, 42102 FB General Status Word - Binary coded2103 32103, 42103 FB Actual Speed 0,01 %2104 32104, 42104 Programmable by P10.1(Default: Frequency reference) - -2105 32105, 42105 Programmable by P10.2(Default: Output frequency) 0,01 +/- Hz2106 32106, 42106 Programmable by P10.3(Default: Motor speed) 1 +/- Rpm2107 32107, 42107 Programmable by P10.4(Default: Motor voltage) 0,1 V2108 32108, 42108 Programmable by P10.5(Default: Motor torque) 0,1 +/- % (of nomi-nal)2109 32109, 42109 Programmable by P10.6(Default: Motor current) 0,01 A2110 32110, 42110 Programmable by P10.7(Default: Motor power) 0,1 +/- % (of nomi-nal)2111 32111, 42111 Programmable by P10.8(Default: DC link voltage) 1 VTable 9.4: Output process dataID Modbus register Name Scale Type2001 32001, 42001 FB Control Word - Binary coded2002 32002, 42002 FB General Control Word - Binary coded2003 32003, 42003 FB Speed Reference 0,01 %2004 32004, 42004 Programmable by P10.92005 32005, 42005 Programmable by P10.92006 32006, 42006 Programmable by P10.92007 32007, 42007 Programmable by P10.92008 32008, 42008 Programmable by P10.9Table 9.5: Input process data