90 • vacon parameters88.15 Fault autoreset parameters (Control panel: Menu PAR -> P14)NOTE! These parameters are shown, when P17.2 = 0.8.16 PID control parameters (Control panel: Menu PAR -> P15)Code Parameter Min Max Unit Default ID NoteAutomatic Reset 0 1 0 731 0 = Disabled1 = EnableWait time 0,10 10,00 s 0,50 717 Waiting time after faultTrial time 0,00 60,00 s 30,00 718 Maximum time for trialsTrials number 1 10 3 759 Maximum trialsRestart Function 0 2 2 7190 = Ramping1 = Flying2 = From Start FunctionTable 8.15: Fault autoreset parametersCode Parameter Min Max Unit Default ID NoteP15.1 Setpoint sourceselection 0 Varies 0 3320 = Fixed setpoint %1 = AI12 = AI23 = ProcessDataIn1(0 -100%)4 = ProcessDataIn2(0 -100%)5 = ProcessDataIn3(0 -100%)6 = ProcessDataIn4(0 -100%)7 = Pulse train/encoder8 = AIE19 = Temperature input 110 = Temperature input 211 = Temperature input 3P15.2 Fixed setpoint 0,0 100,0 % 50,0 167 Fixed setpointP15.3 Fixed setpoint 2 0,0 100,0 % 50,0 168 Alternative fixed setpoint,selectable with DITable 8.16: PID control parametersP14.1P14.2iiP14.3P14.4P14.5