66 • VACON® arfiff08 power generationLocal contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/6.1.3 DC Level SetupUsing these parameters it is possible to modify the awakening level of the drive.P2.1.9.1 DC start levelID 1962When DC rises above this limit when the drive is stopped, DC is considered to be highenough to start-up. If the the DC falls below this level when the drive is stopped, the DCis considered to be too low to produce power and drive will not try to start-up.P2.1.9.2 DC start level delayID 1964Delay for when the DC rises above used DC start level before DC level is considered highenough for starting.P2.1.9.3 DC start level sourceID 1966use the user-set value in P2.1.9.1 asthe Start/Stp Levelltage fromthe previous natural stop + offset from P2.1.9.5 as the new Start Level. The new level isshown in V2.1.9.2P2.1.9.4 DC start level offsetID 1967Offset value to be used when P2.1.9 addedto the open circuit voltage of the DC bus after a stop due to low power production.P2.1.9.5 DC start max limitID 1968Absolute maximum limit for the Start Level when P2.1.9is to make sure adding the offset value after an unsuccessful start-Start Level too high which would make the start-up impossible or to use unreasonablehigh DC level as start limit.