arfiff08 power generation VACON® • 73Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/6.3.1.1 ConfigurationThese signals are used to specify are the G2.3.1 Digital Inputs using Normal or Inverted Logic andwith some input certain specialized parameters also.Note! The Normal/Inverted Logic parameters have no effect on Digital Input which is set to DigIN:0.xP2.3.1.13.1 Input inversionID 1091Bit selection to invert input signal logic.E.g. If you need to invert external fault and surge protection you need to set value 3.B0 (+1): Invert external faultB1 (+2): Invert surge protectionB2 (+4): Invert main contactor feedbackB3 (+8): Invert IO fault resetB4 (+16): Invert DC switch closedB5 (+32): Invert LCL over tempB6 (+64): Invert DC insulationB7 (+128): Invert emergency stopB8 (+256): Invert IO start OKB9 (+512): Invert power limit 1B10 (+1024): Invert power limit 2B11 (+2048): Invert custom DINB12 (+4096): ReservedB13 (+8192): ReservedB14 (+16384): ReservedB15 (+32768): ReservedP2.3.1.13.2 Power limit value 1ID 767Power limit value when DI power limit 1 activateP2.3.1.13.3 Power limit value 2ID 769Power limit value when DI power limit 2 activateP2.3.1.13.4 Custom DIN 1 IDID 771ID number when Custom DIN 1 activate