10 • vacon layout and connectionsTel: +358-201-2121 • Fax: +358-201-212 20533.3 Bus termination resistorsTo assure a proper data transmission, termination of the network segments is required. Dependingon the type of network, either one or two terminations are necessary. Free topology network segmentrequires only one termination whereas a doubly terminated bus topology requires two.The jumper X5 on the Vacon LonWorks board must be set accordingly. Use 94-ohm terminationresistance when only one termination is needed and 47-ohm for two terminations.Figure 3-7. Using jumper X5 to set the bus termination.3.4 LED indicationsThe three LED indications next to the connector show the present statuses of the Neuron (green H3),the LonWorks board (yellow H2) and the Fieldbus Module (green H1). From the user's viewpoint, thefirst two are the most significant.Figure 3-8. LED indications on the LonWorks boardH3 Neuron Service LED GREENH2 Board Status YELLOWH1 Bus Status GREEN212223H3H2H1X5lw1.fh847Ω94Ωno termination X5212223H3H2H1X5lw1.fh8Archived Document