6vacon • 30 CommissioningLocal contacts: https://www.danfoss.com/en/contact-us/contacts-list/Figure 12. STO connection example 2Figure 13. STO connection example 3Cable recommendation:See Table 9 for connections where shielded cable is required. In cases where the shield is markedas being required, use the shield to separate the STO input channels from each other as shown inFigure 14.TypeFor example one of the following:• 2x2x0.75mm 2 (18 AWG) low voltage cable with twoindividually shielded twisted pairs• 2x2x0.75mm 2 (18 AWG) low voltage, unshielded,twisted pair cable• two separate 2x0.75mm 2 (18 AWG) shielded orunshielded twisted pair cables.SAFETY ACTUATOR OPTBJCHANNEL 1SW P+24V+24VOVOVSW MSTO1+STO1-OPTBJCHANNEL 2STO2+STO2-11852_ukSAFETY ACTUATOR OPTBJCHANNEL 1SW P+24V+24VSW PSTO1+STO1-OPTBJCHANNEL 2STO2+STO2-OV11853_uk