8. GAS SUPPLY CONNECTIONA nut and olive are provided for an 8mm pipe inlet connection to the ‘T’ connector atthe bottom front of the appliance. The ‘T’ connector can be rotated to allow aconnection from any direction and includes a valve for isolating the gas supply and apressure test point.The supply pipe must be rigid material. Flexible pipe must not be used.Concealed Supply Pipe ConnectionIf a concealed connection from inside the fireplace is required then, before theappliance is fitted into the fireplace it will be necessary to extend the supply line sothat it will project through the hole in the back of the convection box and run to the ‘T’connector at the front. The pipe run from the supply line up to the rear opening in theconvection box must be kept away from the area which will be taken by theconvection box when it is installed (See figure 7).Note that the centre of the appliance inlet ‘T’ connector is 25mm above the fireplacefloor. The inlet ‘T’ connector should be fitted to the supply pipe at this stage.9. PREPARING APPLIANCE FOR INSTALLATIONIMPORTANTBefore continuing with the installation of this gas fire the aeration setting on theburner must be checked. The aeration is factory set and should not requireadjustment. See section 17.1 (Servicing and parts replacement).1. Unscrew and remove the knurled screwconnecting the slider control arm to theburner module. Lift the slider control knob,moving the control arm away from theburner module.2. Unscrew and remove the left and righthand window brackets (See figure 10).© Baxi Heating U.K. Limited 2008. Page 20Figure 10. Window bracket removalINSTALLER GUIDE