Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting IFSF Wiring to TLS-IB4-41. With AC power switched Off, connect the IFSF network wires to J8 in the TLS-IB as shown in Figure 4-2below:Figure 4-2. Connecting IFSF Network Wiring To TLS-IB2. The LON cable termination jumper (JP3 in Figure 4-2) is shown in the single position (SGL). The singleposition is used when the TLS-IB is a Free Topology Segment in the LON network and only one termination isrequired. The double position (DGL) is used when the TLS-IB is a Doubly Terminated Bus Topology Segmentin the LON network and two terminations are required. To set the jumper in the DGL position, move it to theright (jumper over the middle and right pins).If the TLS-IB is not a terminating device on the IFSF network, you must remove the LONcable termination jumper (JP3) from the board. Failure to do so will result in improperoperation.3. Set the IFSF Node Address DIP switches on the CPU board (S1 in Figure 4-5 on page 4-8) to the desiredNode Address using the table below (U = switch open [up], D= set switch to closed position [down]). Forexample, to enter a IFSF node address of 06, set switches 2 and 4 up, and switches 1 and 3 down.Table 4-1. TLS-IB IFSF Node Address SelectionsIFSFAddressDip Switch Setting1 2 3 401 U U U U02 D U U U03 U D U U04 D D U U05 U U D UOFF+PROBE 4+PROBE 3+PROBE 2+PROBE 1AVERTISSEMENTLA SUBSTITUTION DE COMPOSANTSPEUT COMPROMETTRE LA SECURITINTRINSEQUE.SGL DBLBAWIRING SIDEGJ4D1IFSFJP3J8U8J7L1S1SERVICERAMtlsnt\ibifwr.epsIFSFCLRNMLCLRR12-001331470R12-002R12-003R12-004R12-005R12-006IFSF WiringConnect two wires from IFSFnetwork to the two terminalsof J8 (no polarity).LON Bus TerminationLON bus cable terminationjumper (JP3).NOTICE