Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 TLS-IB Specifications5-8TLS-IB SpecificationsPHYSICAL SPECIFICATIONS• Width w/door closed: 188 mm (7.6”) - Width w/door open: 235 mm (9.6”)• Height: 163 mm (6.7”)• Depth w/door closed: 50 mm (2.6”), Depth w/door open: 228 mm (9”)• Weight: 1.8 kg (3.5 lbs)• The TLS-IB unit contains one CPU/Power Supply board (in unit)• Removable plug type connections• Conduit knockouts for intrinsically-safe wiring: 1/2”, 3/4”, and 1” I.P.S. (2 places)ENVIRONMENTAL SPECIFICATIONS• TLS-IB storage and operation: indoor, climate controlled• Operating temperature range: 0 to +40 °C• Storage temperature range: -40 to +74 °C• LVD and EMC compliant• UL/cUL approved and ATEX approvedELECTRICAL SPECIFICATIONS• TLS-IB operating voltage: 120/240 Vac, 2 A max• Power Supply fuses F1 and F2 are NOT field replaceable. The rating for both fuses is 2 A, Type T (Time Lag)• Intrinsically-safe circuit for scanning Mag ProbesSOFTWARE SPECIFICATIONS• System software upgradeable by a PC program• RAM clear jumper (Figure 5-2 on page 5-3)• Factory boot-up mode for self testing• Supports tank volume reports.• Supports Density and Density OffsetSERIAL COMMUNICATIONS INTERFACE (SCI)• RS-232 or RS-485• Baud rate options: 300, 600, 1200, 2400, 4800, 9600; default 2400• Parity options: None, Odd, Even; default Even• Data length options: 8 or 7; default 7• Number of stop bits options: 1 or 2; default 1