7-5 RegistersMonitor Registers (continued)REGISTER FUNCTION BIT DATA DESCRIPTION(in hex) NO. SET022h Communication Data Link Status 0 1 Write in Progress1 .not used2 not used3 1 Upper/Lower Fault4 1 Consistency Fault5 not used6 not used7 not used8 not used9-15 will return zeros023h Frequency Reference 0-15 units depend on constant n105 (1)024h Output Frequency 0-15 units depend on constant n105 (1)025h Not Used will return zeros026h Not Used will return zeros027h Output Current 0-15 (1 Amp/10) (2)028h Output Motor Voltage 0-15 (1 Volt/1)029h Reserved 0-1502Ah Reserved 0-1502Bh External Terminal Input Value 0 1 Input terminal S1 is closed1 1 Input terminal S2 is closed2 1 Input terminal S3 is closed3 1 Input terminal S4 is closed4 1 Input terminal S5 is closed5 1 Input terminal S6 is closed6 1 not used7 1 not usedNotes:1. Frequency Reference unit (n103) default setting is ‘0’ (0.1Hz / 1).2. Value in register divided by 10 equals actual amps.