10 European StandardsYASKAWA SIEP C730600 86F MECHATROLINK-II Technical Manual 43Code Name Causes Possible SolutionsoFb02 Option Fault An option of the same type is already installed inoption port CN5-A, CN5-B, or CN5-C. Connect the option to the correct option port.oFC00 Option Fault (CN5-B) The option card installed into port CN5-C is notcompatible with the drive.Connect the option to the correct option port.• Note: Use connector CN5-B when connecting DO-A3, AO-A3, or two PG options. Use connector CN5-C whenconnecting only one PG option.To use other options, refer to those option manuals.oFC02 Option Fault An option of the same type is already installed inoption port CN5-A, CN5-B, or CN5-C. Connect the option to the correct option port.■ Minor Faults and AlarmsCode Name Causes Possible SolutionsAEr Station Address Setting Error The node address for the option card is not in thepermitted setting range.Set F6-20 correctly.CALL Serial communication transmissionerror The communications cable wiring is incorrect. • Check for wiring errors.• Correct the wiring.An existing short circuit or communicationsdisconnection Check disconnected cables and short circuits and repair as needed.Programming error on the master side Check communications at start-up and correct programmingerrors.Communication circuitry is damaged. • Perform a self-diagnostics check• If the problem continues, replace either the control board orthe entire drive. For instructions on replacing the controlboard, contact Yaskawa or a Yaskawa representative.CyPo Cycle Power to Active Parameters Comm. Option Parameter Not Upgraded Re-energize the drive to update the communication optionparameters.Note:If the option software version is not compatible or if youinstall an incorrect option to the drive, it will trigger an alarm.◆ Option CompatibilityUsers may connect up to 3 options simultaneously depending on the type of option.Note:You can only connect one option to the GA500. Connect the option card to the CN5 connector.Table 9.10 Option CompatibilityOption Connector Number of Cards PossiblePG-B3, PG-X3 CN5-B, C 2 *1PG-RT3 *2 *3, PG-F3 *2 *3 CN5-C 1DO-A3, AO-A3 CN5-A, B, C 1SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3, SI-ES3, SI-B3, SI-M3, SI-W3 *3, SI-EM3 *3, SI-EN3 *3, SI-EP3,AI-A3 *4, DI-A3 *4 CN5-A 1*1 When connecting two PG option cards, use both CN5-B and CN5-C. When connecting only one PG option card, use the CN5-Cconnector.*2 Not available for the application with Motor 2 Selection.*3 Not available with 1000-Series drive models with a capacities between 450 and 630 kW.*4 When you use the input status of AI-A3 and DI-A3 as a monitor, you can connect AI-A3 and DI-A3 to CN5-A, CN5-B, or CN5-C.10 European StandardsFigure 10.1 CE MarkThe CE mark indicates compliance with European safety and environmental regulations.European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive forelectronics manufacturers, and the EMC guidelines for controlling noise.It is required for engaging in business and commerce in Europe.