www.dadehpardazan.ir 88594014-155 Trial Operation (Checking Linear Servomotor Operation)5.3.1 Setting and Checking the Linear Scale Pitch5-45.3 Setting the SERVOPACK ParametersSet the following SERVOPACK parameters.• Linear scale pitch (Pn282)• Hall sensor selection (Pn080.0)• Motor phase selection (Pn080.1)• Overtravel signal mapping (Pn50A.3, Pn50B.0)• Force limit (Pn483, Pn484)5.3.1 Setting and Checking the Linear Scale Pitch(1) When Using a Serial Converter UnitTurn ON the control power supply.When the power is supplied normally, the panel operator on the front panel of theSERVOPACK will show the following display. A linear scale pitch setting error(A.080) will be displayed, but does not indicate an error. Set the linear scale pitch(Pn282) according to the scale being used. After setting validation of the controlpower, the A.080 alarm will be cleared, and the settings will be enabled.If an alarm other than A.080 is displayed, as shown in the following diagram, the wir-ing for the power supply circuit, the linear servomotor main circuit cable or the cablefor connecting the serial converter unit is the probable cause. Shut down the powersupply, specify the location causing the alarm, and take corrective measures so thatthe display returns to the above normal status. For details on alarms, refer to the cor-responding SERVOPACK or command option module user’s manual (see Manu-als Related to the-V Series in About this Manual.)If the linear scale pitch (Pn282) is not set correctly, the linear servomotor cannot becontrolled. Make sure that the correct value is set before operating the linear servo-motor.Pn282Linear Scale PitchSetting Range Setting Unit Factory Setting When Enabled0 to 6553600 0.01 m 0 After restartNormal statusExample of alarm displaySpeed Position Force