H2 Multi-Function Digital Output SettingsH2-ooSetting Function Description4C During Fast-stop Closed: Fast-stop command is entered4D oH Pre-alarm Time Limit Closed: oH Pre-alarm time limit is passed.4E Braking Transistor Fault (rr) Closed: The built-in dynamic braking transistor failed.Note: Available in drive software versions PRG: 1016 and later.4F Braking Resistor Overheat (oH) Closed: The dynamic braking resistor overheated.Note: Available in drive software versions PRG: 1016 and later.90 to 92 DriveWorksEZ Digital Output 1to 3 These settings are for digital output functions used in DriveWorksEZ.Normally there is no need to change or apply these settings.100 to192H2 Parameter FunctionsReversed Output Switching of 0to 92Reverse the output switching of the multi-function output functions. Setthe last two digits of 1oo to reverse the output signal of that specificfunction.No. Name DescriptionH3: Analog InputsUse H3 parameters to set the multi-function analog input terminals.H3-01 Terminal A1 Signal Level Selection 0: 0 to +10 V (lower limit)1: 0 to +10 V (no lower limit)H3-02 Terminal A1 Function Selection Sets the function of terminal A1.H3-03 Terminal A1 Gain Setting Sets the level of the input value selected in H3-02 when 10V is inputat terminal A1.H3-04 Terminal A1 Bias Setting Sets the level of the input value selected in H3-02 when 0V is inputat terminal A1.H3-09 Terminal A2 Signal Level SelectionSets the input signal level for terminal A2.0: 0 to +10 V (with lower limit)1: 0 to +10 V (no lower limit)2: 4 to 20 mA3: 0 to 20 mAH3-10 Terminal A2 Function Selection Sets the function of terminal A2.H3-11 Terminal A2 Gain Setting Sets the level of the input value selected in H3-10 when 10 V (20mA) is input at terminal A2.H3-12 Terminal A2 Bias Setting Sets the level of the input value selected in H3-10 when 0 V (0 or 4mA) is input at terminal A2.H3-13 Analog Input Filter Time Constant Sets the primary delay filter time constant for terminals A1 and A2.Used for noise filtering.H3-14 Analog Input Terminal EnableSelectionDetermines which analog input terminal or terminals will be enabledwhen a digital input programmed for “Analog input enable” (H1o-oo = C) is activated.1: Terminal A1 only2: Terminal A2 only7: All terminals enabledNote: Available in drive software versions PRG: 1016 and later.B.1 Parameter TableYASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide 187B Parameter List