H2 TIH2 TISetting range: 0 - 200 %Factory setting: 5 %The start-up temperature is determinedby the regulator basedon the following relation:Start-up temp. = (setpoint piglet nest – room temp.) x evaluation + room temperatureExample with valve in the lead, other arrangements possiblePTE / CTERLVLFHMV0 - 10V0 -10V18.09.2008v_ferkln_warmwa_hzng.VSDTFRTFAA3 E2 E1RL ReturnVL FlowMV One or three-way valve (0 - 10 V)TFA Application sensor for water temperature (measured after valve)FH ´Piglet nest heatingTFR Room temperature sensor in stallExample settings• Setpoint for piglet nest: 30 °C• room temperature: 24 °C• Evaluation: 2,90• VT = (30 °C – 24 °C) x 2.90 + 24 °C = 41.4 °C7.6 |Installation| Setpoint derating◄ Setp. derating↑|ESC| P↓IncreaseIncreaseIf the compartment temperature rises above the “setpoint” + the “control range”, thesetpoint is increasedvia an automatic timer per hour by the adjustable value (e.g. 0.2K/h). The increase is only carriedout up to a max. value (adjustable) via “Max. Rising”.Setting range: 0.1...10.0 K/hFactory setting: 0.2 K/hDeratingDeratingIf the compartment temperature sinks below the settings “setpoint” + the “controlrange”, the set point is reset via an automatic timer per hour by the adjustable valuedown to the “normal set point” (“setpoint” in the “Ventilation” menu) (e.g. 0.1 K/h).Setting range: 0.1...10.0 K/hFactory setting: 0.1 K/hOperating Instructions UNIcon / Acontrol The Installation menuL-BAL-E051-GB 1035 Index 003 Part.-No. 00163311-GB26/83