Max. RisingMax. RisingSetting range: 0.0...20.0 KFactory setting: 5.0 KMinimum extraMinimum extraWhile the set point is increased, an (adjustable) tolerance is added to the ventilationminimum (normal).As long as the compartment temperature is greater than the increasedset point, thisresults in a higher ventilation minimum (summer minimum).If the stall temperature drops below the increased setpoint, the function reduces thefeeduntil on dropping below the “normal setpoint” the feedis reducedto “0”. Thisprevents cooling off too much in extreme drops in temperature and still allows goodminimum ventilation.Setting range: 0...100 %Factory setting: 50 %InformationFunction explanation Ventilation – set point derating7.7 |Installation| Sensor adjust◄ Sensor adjust↑|ESC| P↓Adjustment E1Adjustment E1Sensor adjustment for “E1” with a comparator. Enter the difference to the temperaturehere.Setting range: -10.00...+10.00 KFactory setting: 0.0 KAdjustment E2Adjustment E2Sensor adjustment for “E2” with a comparator. Enter the difference to the temperaturehere.Setting range: -10.00...+10.00 KFactory setting: 0.0 KE3Adjustment E3Sensor adjustment for “E3” with a comparator. Enter the difference to the temperaturehere.Setting range: -10.00...+10.00 KFactory setting: 0.0 KAs long as input in IO Setup not activateddisplay: - - - - -Operating Instructions UNIcon / Acontrol The Installation menuL-BAL-E051-GB 1035 Index 003 Part.-No. 00163311-GB27/83