10 Menutables10.1 Main menuInformationThe individually made programming can be saved with PIN 9091 and restored with PIN 9090(Quickinfo Menu- PIN).Attention! Entering PIN 9095 completely resets the device back into its delivered condition. Anychanges that have been made to the settings are thus lost!Enter the individual settings here for tracing!Parameter Factory set-tingCot 1 Cot 2 Cot 3 Cot 4 Cot 5 InformationQuick InfoPIN - - - - - PINs Quickinfo / PINSetpoint 20.0 °CCot On Selection: Off, Preheating, WashingFreshairtemp. 15.0 °CE2 81.6 - - - - -E3 - - - - - - - - - -Max. load- - - - - - - - - -Temp. Min. Value 18.7 - - - - -Temp. Max. Value 25.9 - - - - -Reset Min-Max OFFExhaust air sum 10 %Language DVersion 1.15 - - - - -OTC 00046:37:12 - - - - -OTM 00046:37:12 - - - - -VentilationSetpoint 20.0 °CPband4.0 KMin. ventilation 20 %Max. ventilation 100 %Shutter offset* -1.0 KShutter Pband2.5 KShutter Min. 0 %Shutter Max. 100 %Setp. derating OFFRH setpoint - - - - -RH pband- - - - -RH minimum - - - - -RH maximum - - - - -AlarmAlarm Minimum 10.0 °CAlarm Maximum 35.0°CAlarmdifference 5.0 KAlarm pause 60 minAlarmlist OFFOperating Instructions UNIcon / Acontrol Menu tablesL-BAL-E051-GB 1035 Index 003 Part.-No. 00163311-GB65/83