Parameters 25535.55 Motor thermal timeconstDefines the thermal time constant for use with the motorthermal protection model, defined as the time to reach 63% ofthe nominal motor temperature. See the motormanufacturer's recommendations.256 s100…10000 s Motor thermal time constant. 1 = 1 s3636 Load analyzer Peak value and amplitude logger settings.See also section Load analyzer (page 129).36.01 PVL signal source Selects the signal to be monitored by the peak value logger.The signal is filtered using the filtering time specified byparameter 36.02 PVL filter time.The peak value is stored, along with other pre-selectedsignals at the time, into parameters 36.10…36.15.The peak value logger can be reset using parameter 36.09Reset loggers. The date and time of the last reset are storedinto parameters 36.16 and 36.17 respectively.Output powerNot selected None (peak value logger disabled). 0Motor speed used 01.01 Motor speed used (page 139). 1Output frequency 01.06 Output frequency (page 139). 3Motor current 01.07 Motor current (page 139). 4Motor torque 01.10 Motor torque (page 139). 6DC voltage 01.11 DC voltage (page 139). 7Output power 01.14 Output power (page 140). 8Speed ref ramp in 23.01 Speed ref ramp input (page 200). 10Speed ref ramped 23.02 Speed ref ramp output (page 200). 11Speed ref used 24.01 Used speed reference (page 204). 12Torque ref used 26.02 Torque reference used (page 209). 13Freq ref used 28.02 Frequency ref ramp output (page 213). 14No. Name/Value Description Def/FbEq16100%63%100%TimeTimeMotor thermal timeMotor currentTemperature rise