322 ParametersDifferences in the default values between 50 Hz and 60 Hzsupply frequency settingsParameter 95.20 HW options word 1 bit 0 Supply frequency 60 Hz changes the driveparameter default values according to the supply frequency, 50 Hz or 60 Hz. The bitis set according to the market before the drive is delivered.If you need to change from 50 Hz to 60 Hz, or vice versa, change the value of the bitand then do a complete reset to the drive. After that you have to reselect the macro tobe used.The table below shows the parameters whose default values depend on the supplyfrequency setting. The supply frequency setting, with the type designation of thedrive, also affects Group 99 Motor data parameter values though these parametersare not listed in the table.No Name 95.20 HW options word 1 bitSupply frequency 60 Hz =50 Hz95.20 HW options word 1bit Supply frequency 60 Hz =60 Hz11.45 Freq in 1 at scaled max 1500.000 1800.00015.35 Freq out 1 src max 1500.000 1800.00012.20 AI1 scaled at AI1 max 1500.000 1800.00013.18 AO1 source max 1500.0 1800.022.26 Constant speed 1 300.00 rpm 360.00 rpm22.27 Constant speed 2 600.00 rpm 720.00 rpm22.28 Constant speed 3 900 .00 rpm 1080.00 rpm22.29 Constant speed 4 1200.00 rpm 1440.00 rpm22.30 Constant speed 5 1500.00 rpm 1800.00 rpm22.30 Constant speed 6 2400.00 rpm 2880.00 rpm22.31 Constant speed 7 3000.00 rpm 3600.00 rpm28.26 Constant frequency 1 5.00 Hz 6.00 Hz28.27 Constant frequency 2 10.00 Hz 12.00 Hz28.28 Constant frequency 3 15.00 Hz 18.00 Hz28.29 Constant frequency 4 20.00 Hz 24.00 Hz28.30 Constant frequency 5 25.00 Hz 30.00 Hz28.31 Constant frequency 6 40.00 Hz 48.00 Hz28.32 Constant frequency 7 50.00 Hz 60.00 Hz