Table 50:General settings parameters for the Measurement functionSetting Short description SelectedvalueCommentOperation Operation Off/On On Function must beOnPowAmpFact Amplitude factor to scale powercalculations1.000 Typically no scaling is requiredPowAngComp Angle compensation for phaseshift between measured I & V0.0 Typically no angle compensation isrequired. As well here requireddirection of P & Q measurement istowards protected object (as per IEDinternal default direction)Mode Selection of measured currentand voltageArone Generator VTs are connectedbetween phases (V-connected)k Low pass filter coefficient forpower measurement, V and I0.00 Typically no additional filtering isrequiredVGenZeroDb Zero point clamping in % ofVbase25% Set minimum voltage level to 25%IGenZeroDb Zero point clamping in % ofIbase3 Set minimum current level to 3%VBase (set inGlobal base)Base setting for voltage level inkV15,65 Set generator rated phase-to-phasevoltageIBase (set inGlobal base)Base setting for current level inA3690 Set generator rated current14.2 Gas medium supervision SSIMG (63) GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v314.2.1 IdentificationGUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberInsulation gas monitoring function SSIMG - 6314.2.2 Application GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5Gas medium supervision (SSIMG ,63) is used for monitoring the circuit breakercondition. Proper arc extinction by the compressed gas in the circuit breaker is veryimportant. When the pressure becomes too low compared to the required value, thecircuit breaker operation shall be blocked to minimize the risk of internal failure.Binary information based on the gas pressure in the circuit breaker is used as an inputsignal to the function. The function generates alarms based on the receivedinformation.Section 14 1MRK 505 370-UUS AMonitoring440 Busbar protection REB670 2.2 ANSIApplication manual