Application SEMOD55350-5 v8Generic communication function for Single Point Value (SPGAPC) function is used tosend one single logical output to other systems or equipment in the substation.SP16GAPC can be used to send up to 16 single point values from the applicationfunctions running in the same cycle time. SPGAPC has one visible input andSPGAPC16 has 16 visible inputs that should be connected in the ACT tool.Setting guidelines SEMOD55376-5 v5There are no settings available for the user for SPGAPC.Generic communication function for Measured Value MVGAPC SEMOD55402-1 v3Application SEMOD55872-5 v10Generic communication function for measured values (MVGAPC) function is used tosend the instantaneous value of an analog signal to other systems or equipment in thesubstation. It can also be used inside the same IED, to attach a RANGE aspect to ananalog value and to permit measurement supervision on that value.Setting guidelines SEMOD55424-5 v5The settings available for Generic communication function for Measured Value(MVGAPC) function allows the user to choose a deadband and a zero deadband for themonitored signal. Values within the zero deadband are considered as zero.The high and low limit settings provides limits for the high-high-, high, normal, lowand low-low ranges of the measured value. The actual range of the measured value isshown on the range output of MVGAPC function block. When a Measured valueexpander block (RANGE_XP) is connected to the range output, the logical outputs ofthe RANGE_XP are changed accordingly.17.2.3.2 Receiving data GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v1The GOOSE data must be received at function blocks. There are different GOOSEreceiving function blocks depending on the type of the received data. Refer to theEngineering manual for more information about how to configure GOOSE.Function block type Data TypeGOOSEBINRCV 16 single pointGOOSEINTLKRCV 2 single points16 double pointsGOOSEDPRCV Double pointGOOSEINTRCV IntegerGOOSEMVRCV Analog valueGOOSESPRCV Single pointGOOSEXLNRCV Switch statusSection 17 1MRK 505 370-UUS AStation communication476 Busbar protection REB670 2.2 ANSIApplication manual