Where:1) shows how to connect three secondary phase-to-ground voltages to three VT inputs on theIED2) is the TRM where these three voltage inputs are located. For these three voltage inputs, thefollowing setting values shall be entered:VTprim =132 kVVTsec =110 VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of one individual VT.6666 3110110 3=EQUATION1903 V1 EN-US (Equation 2)3) are three connections made in Signal Matrix Tool (SMT), which connect these three voltageinputs to first three input channels of the preprocessing function block 5). Depending on thetype of functions which need this voltage information, more then one preprocessing blockmight be connected in parallel to these three VT inputs.4) shows that in this example the fourth (that is, residual) input channel of the preprocessingblock is not connected in SMT tool. Thus the preprocessing block will automatically calculate3Vo inside by vectorial sum from the three phase to ground voltages connected to the firstthree input channels of the same preprocessing block. Alternatively, the fourth input channelcan be connected to open delta VT input, as shown in Figure 31.5) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive, negative and zero sequence quantities by using the fundamental frequencyphasors for the first three input channels (channel one taken as reference forsequence quantities)These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the configurationtool. For this application most of the preprocessing settings can be left to the default values.However the following settings shall be set as shown here:VBase=66 kV (that is, rated Ph-Ph voltage)If frequency tracking and compensation is required (this feature is typically required only forIEDs installed in the generating stations) then the setting parametersDFTReference shall beset accordingly.4.2.4.4 Example on how to connect a phase-to-phase connected VT to the IEDSEMOD55055-134 v7Figure 30 gives an example how to connect a phase-to-phase connected VT to the IED.It gives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IED.It shall be noted that this VT connection is only used on lower voltage levels (that is,rated primary voltage below 40 kV).Section 4 1MRK 505 370-UUS AAnalog inputs88 Busbar protection REB670 2.2 ANSIApplication manual