Control Protection Control ProtectionControl and protectionGOOSEen05000734.vsdStation HSIMicroSCADA GatewayIEDAIEDAIEDAIEDAIEDAIEC05000734 V1 EN-USFigure 202: Example of a broadcasted GOOSE message17.2.2 Setting guidelines SEMOD55317-5 v7There are two settings related to the IEC 61850–8–1 protocol:Operation: User can set IEC 61850 communication to Enabled or Disabled.GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sent andreceived. This is only valid for Edition 1 and can be ignored if Edition 2 is used. ForEdition 2, the Ethernet link selection is done with the Ethernet Configuration Tool(ECT) in PCM600.17.2.3 Horizontal communication via GOOSE17.2.3.1 Sending data GUID-9888ECAD-8221-4B31-A443-EB1E3A9022C4 v1In addition to the data object and data attributes of the logical nodes, it is possible tosend the outputs of the function blocks using the generic communication blocks. Theoutputs of this function can be set in a dataset and be sent in a GOOSE Control Blockto other subscriber IEDs. There are different function blocks for different type ofsending data.Generic communication function for Single Point indication SPGAPC,SP16GAPC SEMOD55999-1 v41MRK 505 370-UUS A Section 17Station communicationBusbar protection REB670 2.2 ANSI 475Application manual