10.7.2 ApplicationThe IEC61850 generic communication I/O functions (DPGGIO) function block is used tosend three logical outputs to other systems or equipment in the substation. The three inputsare named OPEN, CLOSE and VALID, since this function block is intended to be used asa position indicator block in interlocking and reservation station-wide logics.10.7.3 Setting guidelinesThe function does not have any parameters available in the local HMI or PCM600.10.8 Single point generic control 8 signals SPC8GGIO10.8.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSingle point generic control 8 signals SPC8GGIO - -10.8.2 ApplicationThe Single point generic control 8 signals (SPC8GGIO) function block is a collection of8 single point commands, designed to bring in commands from REMOTE (SCADA) tothose parts of the logic configuration that do not need complicated function blocks thathave the capability to receive commands (for example SCSWI). In this way, simplecommands can be sent directly to the IED outputs, without confirmation. Confirmation(status) of the result of the commands is supposed to be achieved by other means, such asbinary inputs and SPGGIO function blocks.PSTO is the universal operator place selector for all control functions.Even if PSTO can be configured to allow LOCAL or ALL operatorpositions, the only functional position usable with the SPC8GGIOfunction block is REMOTE.10.8.3 Setting guidelinesThe parameters for the single point generic control 8 signals (SPC8GGIO) function are setvia the local HMI or PCM600.Section 10 1MRK 511 286-UUS AControl266Application manual