Where:1) shows how to connect three secondary phase-to-ground voltages to three VT inputs on the IED2) is the TRM where these three voltage inputs are located. For these three voltage inputs, thefollowing setting values shall be entered:VTprim =66 kVVTsec =110 VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio ofthe entered values exactly corresponds to ratio of one individual VT.6666 3110110 3=EQUATION1903 V1 EN (Equation 22)3) are three connections made in Signal Matrix Tool (SMT), which connect these three voltageinputs to first three input channels of the preprocessing function block 5). Depending on thetype of functions which need this voltage information, more then one preprocessing block mightbe connected in parallel to these three VT inputs.4) shows that in this example the fourth (that is, residual) input channel of the preprocessing blockis not connected in SMT tool. Thus the preprocessing block will automatically calculate 3Voinside by vectorial sum from the three phase to ground voltages connected to the first threeinput channels of the same preprocessing block. .4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequencyphasors for the first three input channels (channel one taken as reference for sequencequantities)These calculated values are then available for all built-in protection and control functions withinthe IED, which are connected to this preprocessing function block in the configuration tool. Forthis application most of the preprocessing settings can be left to the default values. However thefollowing settings shall be set as shown here:VBase=66 kV (that is, rated Ph-Ph voltage)If frequency tracking and compensation is required (this feature is typically required only forIEDs installed in the generating stations) then the setting parametersDFTReference shall beset accordingly.4.2.4.4 Example on how to connect a phase-to-phase connected VT to the IEDFigure 23 gives an example how to connect a phase-to-phase connected VT to the IED. Itgives an overview of the required actions by the user in order to make this measurementavailable to the built-in protection and control functions within the IED as well. It shall benoted that this VT connection is only used on lower voltage levels (that is, rated primaryvoltage below 40 kV).1MRK 511 286-UUS A Section 4Analog inputs73Application manual