11.6 Boolean 16 to integer conversion with logic noderepresentation B16IFCVI11.6.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberBoolean 16 to integer conversion withlogic node representationB16IFCVI - -11.6.2 ApplicationBoolean 16 to integer conversion with logic node representation function B16IFCVI isused to transform a set of 16 binary (logical) signals into an integer. B16IFCVI can receivean integer from a station computer – for example, over IEC 61850–8–1. These functionsare very useful when you want to generate logical commands (for selector switches orvoltage controllers) by inputting an integer number. B16IFCVI has a logical nodemapping in IEC 61850.11.6.3 Setting guidelinesThe function does not have any parameters available in the local HMI or Protection andControl IED Manager (PCM600).11.7 Integer to boolean 16 conversion IB16A11.7.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberInteger to boolean 16 conversion IB16A - -11.7.2 ApplicationInteger to boolean 16 conversion function (IB16A) is used to transform an integer into aset of 16 binary (logical) signals. It can be used – for example, to connect integer outputsignals from one function to binary (logical) inputs to another function. IB16A functiondoes not have a logical node mapping.1MRK 511 286-UUS A Section 11Logic279Application manual