A new recording begins. The view is updated if you leave the menu andreturn.1.2. Navigate to General information or to Trip values to obtain moredetailed information.2. Open the Disturbance handling tool for the IED in the plant structure inPCM600.2.1. Right-click and select Execute manual Trig in the window Availablerecordings in IED.2.2. Read the required recordings from the IED.2.3. Refresh the window Recordings and select a recording.2.4. Right-click and select Create Report or Open With to export therecordings to any disturbance analyzing tool that can handle Comtradeformatted files.Evaluation of the results from the disturbance recording function requires access toa PC either permanently connected to the IED or temporarily connected to theEthernet port (RJ-45) on the front. The PCM600 software package must beinstalled in the PC.Disturbance upload can be performed by the use of PCM600 or by any third partytool with IEC 61850 protocol. Reports can automatically be generated fromPCM600. Disturbance files can be analyzed by any tool reading Comtradeformatted disturbance files.It could be useful to have a printer for hard copies. The correct start criteria andbehavior of the disturbance recording function can be checked when IEDprotective functions are tested.When the IED is brought into normal service it is recommended to delete allrecordings, made during commissioning to avoid confusion in future fault analysis.All recordings in the IED can be deleted in two ways:1. in the local HMI under Main menu/Clear/Reset disturbances, or2. in the Disturbance handling tool in PCM600 by selecting Delete all recordingsin the IED... in the window Available Recordings in IED.13.1.4 Event recorder (ER) and Event list (EL) M12645-2 v6The result from the event recorder and event list can be viewed on the local HMIor, after upload, in PCM600 as follows:1. on the local HMI under Main menu/Events, or in more details via2. the Event Viewer in PCM600.The internal FIFO register of all events will appear when the event viewer islaunched.Section 13 1MRK 502 073-UEN ATesting functionality by secondary injection130 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062Commissioning manual