Trip indication shall be visible in the ICT toolbar.11. Verify that TRIP and ALARM signals are connected to tripping/alarming/signaling/communication in accordance with the scheme design.It is very important that the Function Tripping is Enabled under thefollowing situations:• After completion of the calibration step• Before leaving the ICT Tool7.7 Auditing GUID-70137BAD-6BD5-4835-964E-B6ADAE522A15 v1During installations, calibrations and commissions the ICT generates reports foreach of the steps and collects them under the Auditing tab. See the proceduresbelow on how to view and delete reports as well as generate logs from reports.1. To view the reports, go to the Auditing tab.IEC11000049-1-en.vsdGUID-8348F60B-9BF5-4018-9740-0FA3371B0F9F V1 EN-USFigure 25: Auditing tab2. Open and view each report.3. View reports in one of the following ways:• In the short cut menu, right click and select View report.• Click the View report button in the upper right corner of the auditingscreen.• Double click a report record.4. Delete reports in one of the following ways:Section 7 1MRK 502 073-UEN ACalibrating injection based 100% stator earth fault protection86 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062Commissioning manual