45 V6.70 20131017Press the YES button. The first digit will flash. Use the or arrow buttons toscroll through the digits. Use the or buttons to scroll between the digits.The currently active digit will flash. The first digit will scroll ‘-‘, 0, 1. The seconddigit will scroll 0 to 9 if the first digit is 0, 0 to 6 if the first digit is 1 and last digit is0, 0 to 5 if the first digit is 1 and the last digit is greater than 0. The last digit willscroll 0 to 9 if the first two digits are less than 16. Press YES after you haveentered all digits.After setting the pickup temperature, press the arrow button once:Use the procedure described above to change the drop out setting.The remaining liquid set points can be changed by pressing the arrow buttonand following the above procedure.For programming from a PC just type the desired temperature on the “Enter:” lineas follows:Enter:1/75This will program SP11 pickup to 75C.Enter:2/70This will program SP11 drop out to 70C.4.6.2 Setting Calculated Winding Pickup and Dropout TemperaturesFor units equipped with an Aux CT input, there will be four setpoints, each withan associated pickup and dropout set point. Winding temperature for eachchannel is calculated using the CT current as well as the probe designated asTop Oil. Any of the probes may be designated as top oil. It is important that thewinding calculation be set per Sections 4.4.1 through 4.4.5Set points WSP1, WSP2, WSP3 and WSP4 pickup and drop out temperaturescan be set by the front panel by using the or arrow buttons until the setting025 is displayed:PRGM SETTING 002SP11DRPOUT= 55C