www.baldormotion.com3-20 Basic Installation MN19433.4.10 Power supply filtersTo comply with EC directive 2004/108/EC, an AC power filter of the appropriate type must beconnected. This can be supplied by Baldor and will ensure that the MotiFlex e100 complies withthe CE specifications for which it has been tested. Ideally one filter should be provided for eachMotiFlex e100, except in DC bus sharing applications where only the source drive requires afilter. Filters should not be shared between drives or other equipment. Table 2 lists the appropriatefilters:MotiFlex e100catalognumberRecommendedBaldor ACpower filtersFiltercurrentrating(RMS)MeetsEN61000-6-4Industrial standard(class A)MeetsEN61800-3Drives StandardMFE460A001 FI0035A00 8A No YesMFE460A001 FI0035A01 16A No YesMFE460A003 FI0035A00 8A No YesMFE460A003 FI0035A01 16A No YesMFE460A006 FI0035A01 16A No YesMFE460A010 FI0035A01 16A No YesMFE460A010 FI0035A02 25A Yes YesMFE460A016 FI0035A02 25A Yes YesFI0035A03 36A Yes YesMFE460A021 FI0035A04 50A No YesFI0035A05 66A No YesFI0035A03 36A Yes YesMFE460A026 FI0035A04 50A No YesFI0035A05 66A No YesMFE460A033 FI0035A04 50A No YesMFE460A033 FI0035A05 66A No YesMFE460A048 FI0035A05 66A Yes YesMFE460A065 FI0035A05 66A Yes YesTable 2 - Baldor filter part numbersFor filter earth leakage figures, see section 3.4.3.Note: The MotiFlex e100 is not intended to be used on a low-voltage public networkwhich supplies domestic premises. Radio frequency interference is expected ifused on such a network.