9424200994 Rev N 315A Page Setup icon is also provided on the BESTlogicPlus Programmable Logic toolbar allowing you toselect Paper Size, Paper Source, Orientation, and Margins.Clearing the On-Screen Logic DiagramClick the Clear button to clear the on-screen logic diagram on all logic pages and start over.BESTlogic™Plus ExamplesExample 1 - OR Gate ConnectionsFigure 238 illustrates a typical OR gate connection. In this example, OUT5 will become active when eitherthe Major Alarm OR the Minor Alarm OR both is true.Figure 238. Example 1 - OR Gate ConnectionsExample 2 - Inverse Overcurrent Logic DiagramFigure 239 illustrates a typical logic diagram of two inverse overcurrent elements set up to trip outputsand trigger fault reports. The 51-1 function is blocked when IN1 is true. The 51-1 function is blocked whenIN2 is true. OUT1 is true when either the 51-1 or 51-2 is in a trip condition. OUT2 is true when either the51-1 or 51-2 is in a pickup condition. The fault trigger logic block ensures that faults are recorded.Figure 239. Example 2 - Inverse Overcurrent Logic DiagramBE1-11g BESTlogic™Plus