9424200994 Rev N 631Figure 385. Module 1 Input #1 ScreenTable 257 summarizes the configuration settings for remote analog inputs.Table 257. Configuration Settings for Remote Analog InputsSetting Range Increment Unit of Measure DefaultLabel Up to 64 alphanumeric characters n/a n/a Module 1Input 1Type Voltage or Current n/a n/a VoltageParam Min –99,999.9 to 99,999.9 0.1 n/a –99,999.9Param Max –99,999.9 to 99,999.9 0.1 n/a –99,999.9Min Input Current 4 to 20 0.01 milliamps 4Max Input Current 4 to 20 0.01 milliamps 20Min Input Voltage 0 to 10 0.01 volts 0Max Input Voltage 0 to 10 0.01 volts 10Remote Analog Outputs ConfigurationThe RTD module provides four analog outputs. The BE1-11g supports two RTD modules at once.Configuration SettingsBESTCOMSPlus Navigation Path: Settings Explorer, Programmable Outputs, Remote Analog OutputsHMI Navigation Path: Settings Explorer, Analog OutputsConfiguration settings are made using the BE1-11 plugin for BESTCOMSPlus. To program theconfiguration settings, use the Settings Explorer to open the Programmable Outputs, Remote AnalogOutputs tree branch and select the module and output to be modified. Refer to Figure 386. Use the drop-down menu under Param Selection to select a parameter. Select the Output Type. The analog outputsare always monitored and their status is displayed on the appropriate metering screens. The BE1-11greports Out of Range when an RTD module is disconnected.Ranges must be set for the selected output type. Param Min correlates to Min Output Current or MinOutput Voltage and Param Max correlates to Max Output Current or Max Output Voltage.BE1-11g RTD Module