9424200994 Rev N 383Table 131. Definite Time Verification Test SettingsSetting Value DescriptionInverse Time Pickup 0 Disables Inverse Time PickupDefinite Timer 1 Pickup 2.36 Sets Definite Timer 1 Pickup at 118% of nominal (2.36 V/Hz)Definite Timer 1 Time Delay 500 Sets Definite Timer 1 Time Delay at 500 msAlarm Pickup 0 Disables Alarm PickupStep 2: Connect and apply 120 Vac, three-phase, 60-hertz voltage source to Terminals C13 (A-phase),C14 (B-phase), C15 (C-phase), and C16 (neutral).Step 3: Step the A-phase voltage to 142.2 V (118.5% or 2.37 V/Hz). Measure the time between theincrease in voltage and the closure of OUT1. Record the result.Step 4: Repeat steps 1 through 3 for Time Delays of 1 second and 5 seconds. Record the results.Step 5: (Optional.) Repeat steps 1 through 4 for the B-phase and C-phase voltage inputs.Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.Step 7: (Optional.) Set Definite Timer 1 Pickup to 0 and Definite Timer 2 Pickup to 2.36 V/Hz and repeatsteps 1 through 6 for Definite Timer 2.Functional Test ReportAlarm VerificationAlarm Setting Range = 0.5 to 6 V/HzAlarm Accuracy = ±2% or ±0.05 V/Hz, whichever is greaterAlarm/Reset Ratio = 98% ±1%Step AlarmSetting Low ActualAlarm High Low* ActualReset High* Pass/Fail6 2.05 2.00 V/Hz 2.10 V/Hz 1.94 V/Hz 1.98 V/Hz P / F* Reset range is calculated from the alarm setting and may need adjusted based on actual alarm.Inverse Time Pickup VerificationPickup Setting Range = 0.5 to 6 V/HzPickup Accuracy = ±2% or ±0.05 V/Hz, whichever is greaterDropout/Pickup Ratio = 98% ±1%Step PickupSetting Low ActualPickup High Low* ActualDropout High* Pass/Fail7 2.10 2.05 V/Hz 2.15 V/Hz 2.037 V/Hz 2.079 V/Hz P / F* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.Definite Time Pickup VerificationPickup Setting Range = 0.5 to 6 V/HzPickup Accuracy = ±2% or ±0.05 V/Hz, whichever is greaterDropout/Pickup Ratio = 98% ±1%BE1-11g Overexcitation (24) Test