en_BA_RR30_IO-Link_V0.23.docx 19/40 Baumer Electric AG13.01.2021/ Frauenfeld, SwitzerlandIn section 3.1, the signal path is described more detailed, to illustrate how the counter module isimplemented. In section 4.3.8.2 the behavior is explained.4.3.8.1 SSC4 ConfigurationIn general the SSC4 offers the same features as the SSC1 and SSC2 based on distance (See 4.3.2),including also time filters.Exceptions:- No hysteresis settings as there are only incremental counts.- Additional parameters to adjust like SSC4 Source and SSC4 Auto-Reset.Parameter name Short Description Rights Unit / Allowed valuesSSC4 Param.SP1 Set the number of counts at whichthe SSC is set to active (orinactive if inverted)rw 0 … max = 2147483639Counts, default 20SSC4 Param.SP2 Set the number of counts at whichthe SSC is set to inactive (oractive if inverted). only active ifSSC is set to window moderw 0 … max = 2147483639Counts, default 0Parameter name Short Description Rights Unit / Allowed valuesSSC4 Config.Logic Selects the SSC logic. It can bechanged between active if objectis present (normal) or inactive ifobject is present (inverted)rw - Normal (Default)- InvertedSSC4 Config.Mode Selection of the switching mode rw - Disabled (Default)- Single Point- WindowSSC SourceSettings.SSC4 SelectionSelect the switch counter that isused as input of SSC4rw - SSC1 Switch Counter(Default)- SSC2 Switch CounterSSC SourceSettings.SSC4 AutoResetAuto Reset of switch counter ifvalue in SSC4 Param.SP1 isreachedrw - Enabled (Default)- DisabledParameter name Short Description Rights Unit / Allowed valuesRelease Delay.SSC4TimeSets / indicates the release delaytime in milliseconds for therespective switching signalchannel (SSC).rw 0 to 60000 msDefault: 0 msResponse Delay.SSC4TimeSets / indicates the responsedelay time in milliseconds for therespective switching signalchannel (SSC).rw 0 to 60000 msDefault: 0 msMinimal PulseDuration.SSC4 TimeSets / indicates the minimal pulselength in milliseconds for therespective switching signalchannel (SSC).rw 0 to 60000 msDefault: 0 msMinimal PulseDuration.SSC4 Mode0: Both Pulses: positive andnegative pulses are prolonged; 1:Positive Pulse: only positivepulses are prolonged; 2: Negativerw - Both Slopes (Default)- Positive Slope- Negative Slope