6 - SETTING UP TOUCH PILOT CONTROL6.1 - General descriptionTouch Pilot includes the 7 in. touch screen allowing for easy systemcontrol. Navigation through the Touch Pilot control is either usingthe touch screen interface or by connecting to the web interface.The navigation menus are the same for both connection methods(Touch Pilot user interface and web browser). It is recommendedto use a stylus pen for the navigation via the touch screen.NOTE: Some functions are unavailable when using the webbrowser interface.The Touch Pilot interface includes the following screens:- Welcome screen- Synoptic screen- Operating mode selection screen- Data/configuration screens- Password entry and language selection screen- Alarms screen- Parameter modification screen6.2 - Welcome screenThe Welcome screen is the first screen shown after starting theuser interface. It displays the application name as well as thecurrent software version number.To exit the Welcome screen and go to the Home screen(see section 6.3), press the Home button.Legend1. Home button2. Software version number3. Information message boxInformation message box: The information displayed in the statusbar at the bottom of the screen includes relevant messagesregarding the current user action.Message StatusCOMMUNICATIONFAILURE!Equipment controller did not respond whilereading the table content.ACCESS DENIED! Equipment controller denies access to one ofthe tables.LIMIT EXCEEDED! The value entered exceeds the parameter limit.Save changes? Modifications have been made. The exit mustbe confirmed by pressing "Save" or "Cancel".HIGHER FORCE INEFFECT!Equipment controller rejects Force or Autocommand.Too many usersconnected ! Pleasetry again later ...Too many users connected at the same time(WEB INTERFACE ONLY)6.3 - Synoptic screenThe Synoptic screen allows you to monitor the vapour-refrigerationcycle. The diagram indicates the current status of the unit, givinginformation on the unit capacity, the status of water heat exchangerpumps, and the pre-defined setpoint parameter.All unit functions can be accessed by pressing the Main menubutton.Example: Synoptic view. This picture is for information only.It may differ from the actual look, depending on pumps and OAT sensor availability.Legend1. Home button2. Main menu button3. Login button (restricted access to menus)4. Start/Stop button5. Alarm button6. Compressor + unit capacity7. LWT and EWT (condenser)8. Setpoint9. Unit running status10. LWT and EWT (evaporator)6.4 - Unit start/stopWith the unit in the Local off mode:• To display the list of operating modes and select the requiredmode, press the Start/Stop button in the upper-right cornerof the Synoptic screen.IMPORTANT: When entering the menu, please note that thecurrently selected item corresponds to the last runningoperating mode.(1)(2)(3)(6)(2)(1) (3) (4) (5)(7)(8)(9)(10)11