7.2 - Configuration menu (CONFIG1)Icon Displayed text* Description NameGeneral Configuration General configuration parameters GEN_CONFPump Configuration Pump configuration PUMPCONFUser Configuration User configuration USERCONFReset Configuration Reset configuration RESETCFGSchedule Menu Schedule settings SCHEDULEHoliday Menu Holiday settings HOLIDAYDate/Time configuration Date/Time settings DATETIME*Displayed in English by default.CAUTION: Since specific units may not include additionalfeatures, some tables may contain parameters that cannotbe configured for a given unit.General Configuration Menu – GEN_CONFNo. Name Status Default Unit Displayed text * Description1 prio_cir 0 to 2 0 - Cir Priority Sequence Circuit priority2 0=Auto, 1=A Prio 0 = Automatic circuit selection1 = Circuit A priority3 2=B Prio 2 = Circuit B priority4 ramp_sel no/yes no - Ramp Loading Select Ramp loading selection5 off_on_d 1 to 15 1 min Unit Off to On Delay Unit Off to On delay6 lim_sel 0 to 2 0 - Demand Limit Type Select Demand limit type7 0 = None 0 = None8 1 = Switch Control 1 = Switch control9 2 = 4-20mA Control 2 = 4-20mA control10 nh_start 00:00 00:00 - Night Mode Start Hour Night mode start hour11 nh_end 00:00 00:00 - Night Mode End Hour Night mode end hour12 nh_limit 0 to 100 100 % Night Capacity Limit Night capacity limit13 curr_sel no/yes no - Current Limit select Current limitation select14 ice_cnfg no/yes no - Ice Mode Enable Ice mode15 curr_max 0 to 4000 2000 A Maximum Current Limit Maximum current limitation16 shortcyc no/yes no - short cycle management Short cycle management17 al_rever no/yes no - Reverse Alarms Relay Reverse alarm/alert signals18 capre_en no/yes no - Enable capacity recovery Capacity recovery in case of power outage19 capre_t 0 to 10 0 min Capa rec max off time Maximum time with power off for capacity recovery*Displayed in English by default.7 - DETAILED MENU STRUCTURE22