Pump Configuration Menu – PUMPCONFNo. Name Status Default Unit Displayed text * Description1 hpumpseq 0 to 1 0 - Condenser PumpsSequenceCondenser pumps sequence2 cpumpseq 0 to 1 0 - Cooler Pumps Sequence Cooler pumps sequence3 0 = No Pump 0 = no pump4 1 = One Pump Only 1 = one pump only5 pump_per no/yes no - Pump Sticking Protection Pump anti-sticking protection6 pump_sby no/yes no - Stop Pump During Standby Pump stopped during standby7 pump_loc no/yes yes - Flow Checked If Pump Off Water flow is checked when the pump is off8 stopheat no/yes no - Cooler Pump Off In Heat Cooler pump is off when the unit is in Heating9 stopcool no/yes no - Cond Pump Off In Cool Condenser pump is off when the unit is in Cooling*Displayed in English by default.Reset Configuration Menu – RESETCFGNo. Name Status Default Unit Displayed text * Description1 cr_sel 0 to 4 0 - Cooling Reset Select Reset source in Cooling2 hr_sel 0 to 4 0 - Heating Reset Select Reset source in Heating3 0=None, 1=OAT 0 = None1 = OAT4 2=Delta T, 4=Space Temp 2 = Delta T4 = Space temperature5 3=4-20mA control 3 = 4-20 mA signal67 Cooling Cooling8 oat_crno -10 to 51.714 to 125-1014°C°FOAT No Reset Value OAT, no reset value(applies to units with a Dry Cooler at the condenser)9 oat_crfu -10 to 51.714 to 125-1014°C°FOAT Full Reset Value OAT, max. reset value(applies to units with a Dry Cooler at the condenser)10 dt_cr_no 0 to 13.90 to 2500^C^FDelta T No Reset Value Delta T, no reset value11 dt_cr_fu 0 to 13.90 to 2500^C^FDelta T Full Reset Value Delta T, max. reset value12 v_cr_no 0 to 20 0 mA Current No Reset Value Current, no reset value13 v_cr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value14 spacr_no -10 to 51.714 to 125-1014°C°FSpace T No Reset Value Space temperature, no reset value15 spacr_fu -10 to 51.714 to 125-1014°C°FSpace T Full Reset Value Space temperature, max. reset value16 cr_deg -16.7 to 16.7-30 to 3000^C^FCooling Reset Deg. Value Cooling reset value1718 Heating Heating19 oat_hrno -10 to 51.714 to 125-1014°C°FOAT No Reset Value OAT, no reset value(applies to units with a DryCooler at the condenser)20 oat_hrfu -10 to 51.714 to 125-1014°C°FOAT Full Reset Value OAT, max. reset value(applies to units with a DryCooler at the condenser)21 dt_hr_no 0 to 13.90 to 2500^C^FDelta T No Reset Value Delta T, no reset value22 dt_hr_fu 0 to 13.90 to 2500^C^FDelta T Full Reset Value Delta T, max. reset value23 v_hr_no 0 to 20 0 mA Current No Reset Value Current, no reset value24 v_hr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value25 spahr_no -10 to 51.714 to 125-1014°C°FSpace T No Reset Value Space temperature, no reset value26 spahr_fu -10 to 51.714 to 125-1014°C°FSpace T Full Reset Value Space temperature, max. reset value27 hr_deg -16.7 to 16.7-30 to 3000^C^FHeating Reset Deg. Value Heating reset value*Displayed in English by default.7 - DETAILED MENU STRUCTURE23