78 Installation (for qualified installers only)© Travis Industries 6/19/18 - 1418 DaVinci-Cat2+Termination Requirements! Venting terminals shall not be recessed into a wall or siding.A Minimum 9" (229mm) clearance from any door or windowB Minimum 24" (610mm) above any grade, veranda, porch, deck or balconyC Minimum 1" (25mm) from outside corner wallsNOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.D Minimum 24" (610mm) from inside corner wallsNOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.E Minimum 24" (610mm) clearance below ventilated or unventilated soffits or roof surfacesNOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.F Minimum 12" (305mm) clearance below a veranda, porch, deck or balconyNOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minumum of two sides beneath the floor.NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.G Minimum 48" (1219mm) clearance from any adjacent buildingH Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or drivewaysNOTE: may not be used over a walkway or driveway shared by an adjacent buildingI Minimum 12" (305mm) clearance to any nonmechanical air supply inlet to the building or the combustion air inletto any other appliance (36” 914mm if over 100,000 BTUs in Canada)J Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10’ (3M) horizontallyEXCEPTION: The air intake for this fireplace may be placed a minimum 24” (610mm) to the side or below theexhaust termination (do not place the intake above the exhaust termination).K Minimum 36" (914mm) from the area above the meter/regulator (vent outlet) - this extends 15’ (4.5M) above theregulatorNOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.L Minimum 36" (914mm) from the meter/regulator (vent outlet)NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.M Minimum 12” (305mm) above the roof line (for vertical terminations)N Minimum 24” (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations• Vent termination must not be located where it will become plugged by snow or other materialCBHEG ADFLK JINOTE: Measure clearances to the nearest edge of the exhaust hood.AEEMN