Air and Water cooled inverter chillers and heat pumpEWAD TZ - EWAD TZ B - EWWD VZAir and Water cooled inverter chillersand heat pumpD-EOMZC00105-17ENOperation Manual21/844 MENU STRUCTUREAll settings are divided in different menus. Each menu collects in a single page other sub-menus, settings ordata related to a specific function (for example Power Conservation or Setup) or entity (for example Unit orCircuit). In any of the following pages, a grey box will indicate changeable values and the defaults.4.1 Main MenuSetpoint/Sub-Menu Default Range DescriptionEnter Password - Submenu to activate access levelsView/Set Unit - Submenu for unit data and settingsView/Set Circuit - Submenu for circuit data and settingsUnit Status= Off: Unit Sw AutoOff: Ice Mode TmrOff: OAT Lockout (A/C units only)Off: All Cir DisabledOff: Unit AlarmOff: Keypad DisableOff: Master DisableOff: BAS DisableOff: Unit SwOff: Test ModeOff: Schedule DisableAuto: Noise ReductionAuto: Wait For LoadAuto: Evap Recirc (A/C units only)Auto: Water Recir (W/C units only)Auto: Wait For FlowAuto: PumpdnAuto: Max PulldnAuto: Unit Cap LimitAuto: Current LimitStatus of the UnitActive Setpoint= 7.0°C, - Water temperature active setpoint + link to Setpoint pageMS Ctrl Tmp= -273.1°C, - Master slave controlled temperature + link to Master SlaveData pageEvaporator LWT= -273.1°C, - Evaporator leaving water temperature + link to TemperaturespageCondenser LWT= -273.1°C, - Condenser leaving water temperature + link to Temperaturespage (W/C units only)Unit Capacity= 0.0%, - Unit capacity + link to Capacity pageUnit Mode= Cool, - Unit Mode + link to Available modes pageUnit Enable= Enable, - Unit Enable state + link to unit and circuits enable pageTimers - Submenu for unit timersAlarms - Submenu for alarms; same function as Bell ButtonCommission Unit - Submenu for commission unitAbout Chiller - Application Info submenu4.2 View/Set UnitSetpoint/Sub-Menu Default Range DescriptionThermostat Ctrl - Submenu for Thermostatic controlNetwork Ctrl - Submenu for Network controlVfd Settings - Submenu Vfd installation settings (A/C units only)Pumps - Submenu for pump settingsCondenser - Submenu for Condenser tower control (W/C units Only)Master/Slave - Submenu for Master Slave data and settingsRapid Restart - Submenu for Rapid Restart OptionDate/Time - Submenu Date, Time and Quiet Night mode scheduleScheduler - Submenu for Time SchedulerPower Conservation - Submenu Unit Limiting functionsElectrical Data - Submenu for electrical dataCtrl IP Setup - Submenu for controller IP-address setupDaikin on Site - Submenu for connection to Daikin cloud DoSMenu Password - Submenu Disable Password for User level4.2.1 Thermostat CtrlThis page resumes all the parameters related to the unit thermostatic control.