Air and Water cooled inverter chillers and heat pumpD-EOMZC00105-17ENOperation Manual22/84EWAD TZ - EWAD TZ B -EWWD VZAir and Water cooled inverter chillers andheat pumpSetpoint/Sub-Menu Default Range DescriptionTZ/TZ B VZStart Up DT= 2.7°C 2.7°C 0.0…5.0°C Offset to start thermostat controlShut Dn DT= 1.0°C 1.5°C 0.0…1.7°C Offset to standbyStg Up DT= 0.5°C 0.5°C 0.0…1.7°C Offset to allow compressor startsStg Dn DT= 1.0°C 0.7°C 0.0…1.7°C Offset to force one compressor offStg Up Delay= 5 min 3 min 0…60 min Compressor start interstageStg Dn Delay= 3 min 3 min 3…30 min Compressor stop interstageStrt Strt Dly= 20min 15min 15…60 min Compressor Start to Start delayStop Strt Dly= 5min 3min 3…20 min Compressor Stop to Start delayIce Cycle Dly= 12h 12h 1…23h Ice cycle delayLt Ld Stg Dn %= 40% 20% 20…50% Circuit capacity threshold to stage down one compressorHi Ld Stg Up %= 80% 50% 50…100% Circuit capacity threshold to stage up one compressorMax Ckts Run= 2 2 1…2 Limit to the number of circuit to be usedC1 Sequence #= 1 1 1…2 Manual sequence of circuit #1C2 Sequence #= 1 1 1…2 Manual sequence of circuit #2Next Crkt On= 0 0 - Shows next circuit to be started upNext Crkt Off= 0 0 - Shows next circuit number to be stopped4.2.2 Network CtrlThis page resumes all settings related to Network control.Setpoint/Sub-Menu Default Range DescriptionTZ / TZ B VZControl Source= Local Local Local, Network Local Network control selectionAct Ctrl Src= Local N/A Local, Network Actual control between Local, NetworkNetwrk En SP= Disable Disable Enable, Disable Enable unit command from BMSNetwrk Mode SP= Cool Cool - Cool, Ice, Heat (NA), Cool/Heat RecoveryNetwrk Cool SP= 6.7°C 6.7°C - Cooling setpoint from BMSNetwrk Cap Lim= 100% 100% - Capacity limitation from BMSNetwrk HR SP= 45.0°C N/A - Heat recovery setpoint from BMSNetwork Heat SP= N / A 45.0°C - Heating setpoint from BMS (W/C Units only)Netwrk Ice SP= -4.0°C -4.0°C - Ice setpoint from BMSNetwrk Current SP= 800A 800A - Sepoint for current limitation from BMSRemote Srv En= Disable Disable Enable, Disable Remote server enable4.2.3 Compressor Vfd Setup (A/C Units only)This page contains basics Vfd Settings. It will be possible to set the Modbus address of each inverter installedon compressors. This function is supposed to be activated in case of compressor replacement. The page willalso contain the Modbus setup parameters like baud rate, parity etc.Setpoint/Sub-Menu Default Range DescriptionBaud Rate= 19200 4800, 9600, 19200, 38400 Modbus communication speedParity= None None, Odd, Even ParityTwo Stop Bits= No No, Yes Number of stop bits485 Resistance= Active Active, Passive RS485 Termination resistanceSet Inv1 Fltr= Hold Hold, Exec Command to enable communication filter on the compressor 1Set Inv2 Fltr= Hold Hold, Exec Command to enable communication filter on the compressor 24.2.4 PumpsThis page contains the settings to define the operation of the primary/backup pumps, the running hours ofeach pump and all parameters to configure the behavior of the pump driven with an inverter.Setpoint/Sub-Menu Default Range DescriptionTZ / TZB VZEvp Pmp Ctrl= #1 Only #1 Only #1 Only, #2 Only, Auto,#1 Primary, #2 PrimarySet number of Evaporator pumps operational and whichpriority.Evap Recirc Tm= 30s 30s 0…300s Water recirculating timerEvap Pmp 1 Hrs= 0h 0h Running Hours Evaporator Pump 1 (if present)Evap Pmp 2 Hrs= 0h 0h Running Hours Evaporator Pump 2 (if present)Speed 1= 80% N/A 0-100% Speed when the input Double Speed Switch is openCnd Pump Ctrl= N/A #1 Only #1 Only, #2 Only, Auto,#1 Primary, #2 PrimarySet number of Condenser pumps operational and whichpriority.