SiEBE18-526 Field SettingTest Operation 123Image of operation in the case of AImage of operation in the case of BImage of operation in the case of A and B(V3081)Power consumptionRated power consumption80 % of rated power consumption70 % of rated power consumption60 % of rated power consumption40 % of rated power consumptionForced thermostat OFF(Fan operation)Demand level 1 instructingPower consumption set by"Demand 1 level setting".Demand level 2 instructing Demand level 3 instructingThe powerconsumption duringthe demand level 1instructing can beset with the"Demand 1 levelsetting".("70 % of ratedpower consumption"has been set atfactory.)(V3082)The power consumption set with "Demand 1 level setting".When the"Continuous demandsetting" is set to ON("OFF" has been setat factory.) , thepower consumptioncan be set with the"Demand 1 levelsetting". ("70 % ofrated powerconsumption" hasbeen set at factory.)?Power consumptionRated power consumption80 % of rated power consumption70 % of rated power consumption60 % of rated power consumption40 % of rated power consumptionForced thermostat OFF(Fan operation)(V3083)The power consumption set with "Demand 1 level setting".HDemand level 2 instructing HDemand level 3 instructingThe powerconsumption can beset with the"Demand 1 levelsetting". ("70 % ofrated powerconsumption" hasbeen set at factory.)HDuring continuous demand operation,when the external demand instruction isreceived repeatedly, the instruction withhigher demand level has the precedence.Power consumptionRated power consumption80 % of rated power consumption70 % of rated power consumption60 % of rated power consumption40 % of rated power consumptionForced thermostat OFF(Fan operation)