Field Setting for SkyAir Indoor Unit SiEBE18-526136 Test Operation4.6 Centralized Group No. Setting If carrying out centralized control with a central remote controller and unified ON/OFFcontroller, you have to set the group No. for each group by remote controller. To set the group No., first turn on the power supply of the central remote controller, unifiedON/OFF controller and indoor unit.CentralizedGroup No. Settingby RemoteController1. If the inspection/test button is pushed for 4 seconds or more when in the normal mode,operation enters the “field set mode.”2. Using the temperature control buttons, set the mode No. to “00.”3. Push the inspection/test button to inspect the group No. display.4. Using the programming time button, set the group No. for each group. (Group No. rises inthe order of 1-00, 1-01, ...1-15, 2-00 ...4-15, etc. The unified ON/OFF controller howeverdisplays only the range of group numbers selected by the switch for setting each address.)5. Push the timer ON/OFF button and enter the selected group No.6. Push the inspection/test button and return to the normal mode.∗ If the address has to be set individually for each unit for power consumption counting, etc., setthe mode No. to “30.”Group No. SettingExampleNote: 1. “F1,F2” indicates interface adaptor for SkyAir series.2. If not using remote controllers, temporarily connect a remote controller to set the group No.,set the group No. for centralized control, and then disconnect the controller.Group No.MODE NO.FIELDSETMODE(S1095)Central remote controlUnified ON/OFF controllerNo remote controlRemote control centralized control(automatic address)Group No. forcentralizedcontrolF 1F2F1 F2P1·P2F 1 F 2P1·P2F1 F2P1·P2F1 F2P1·P2F1 F 2P1·P2 P1·P2 P1·P2Indoor unit1-00 1-01 1-021-03 1-04 (S1946)