SiEBE18-526 Field Setting for SkyAir Indoor UnitTest Operation 1314.4 Local Setting Mode NumberExample To set the filter sign time to “filter contamination - heavy” for all units in a group:Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”Table (FHQ & FFQ)Note: 1. Setting is made in all units in a group. To set for individual indoor units or to check thesetting, use the mode Nos. (with “2” in upper digit) in parentheses ( ).2. The setting position No. is set to “01” at the factory, except for the following cases in which“02” is set. Setting of air flow direction adjustment range 13(23)-4 Automatic restart after power outage. 12(22)-5 Remote control thermostat 10(20)-2 Filter sign indication (only for ceiling-mounted duct type) 10(20)-33. Since drafts may result, carefully select the installation location.4. When power returns, units resume the settings made before the power failure.Caution When “auto restart after power failure reset” is set, be sure to turn off air conditioners, then cutoff the power supply before conducting maintenance, inspection and other work. If the powersupply is cut off with the power switch left ON, air conditioners will automatically start operatingwhen the power supply is turned on.5. Do not set any items other than those listed in the above table.6. Functions that indoor units are not equipped with will not be displayed.7. When returning to normal mode, “88” may be displayed on the LCD section of the remotecontroller due to initialization operation.ModeNo.Note 1SettingSwitchNo.Setting Description Setting Position No. *Note 201 02 0310(20) 0 Filter contamination - heavy /light (Setting of operatinghours for filter sign indication)(Change setting whenreducing filter sign indicationtime to half due to quick soilingof filter)Long-LifeType Light Approx.2,500hoursHeavy Approx.1,250hours—1 Long-life filter type (Setting of filter signindication time)(Change setting when Ultra-long-life filter isinstalled)Long-Life Filter — —2 Remote control thermostat(Set when remote control thermostat sensoris used.)Use Not use3 Estimation of filter operating hour(Change setting when filter sign indication isnot used)ON OFF —11(21)2 Indoor unit fan OFF when thermostat OFF incooling/heating— Fan OFF —12(22)5 Automatic restart after power failure reset*Note 4OFF ON —13(23)0 HighCeilingCeiling-suspended type(FHQonly)2.7 m or Lower 2.7~3.5 m —1 Air flow direction selection (Change settingwhen blocking kit is installed) *Note 3F T W4 Setting of air flow direction adjustmentrangeUpward Standard Downward