Field Setting for SkyAir Indoor Unit SiEBE18-526130 Test Operation4.2.2 Wireless Remote ControllerNote: If optional accessories are mounted on the indoor unit, the indoor unit setting may have to bechanged. Refer to the instruction manual (optional hand book) for each optional accessory.Procedure 1. When in the normal mode, push the “ ” button for a minimum of four seconds,and the FIELD SET MODE is entered.2. Select the desired MODE NO. with the “ ” button.3. Push the “ ” button and select the FIRST CODE NO.4. Push the “ ” button and select the SECOND CODE NO.5. Push the “ ” button and the present settings are SET.6. Push the “ ” button to return to the NORMAL MODE.4.3 Initial Setting ContentsMODE NO.FIELD SET MODE345SECOND CODE NO.FIRST CODE NO.2(S1934)1, 6Setting ContentsIndoor ModelsFilterSign Filter SignEstimation ofAccumulatedOperatingHoursHigh AirOutletVelocity(forApplicationto CeilingHigherthan 2.7m)Selectionof AirFlowDirectionF, T, WAir FlowDirectionAdjustAir FlowDirectionRangeSettingExternalStaticPressureLongLifeFilterTypeFanSpeedUpSimul-taneousoperation(Twin)CeilingSuspendedtype(FHQ)(HeatPump)FHQ35~60BUV1B{ { {CeilingMountedCassettetype(FFQ)(HeatPump)FFQ25~60BV1B{ { { { { {