SiUS331604E Field Setting from Remote ControllerField Setting 90(11) Compensating the Floor Temperature(When the unit is equipped with an infrared floor sensor)Offset the detected value of the infrared floor sensor with a certain temperature. This setting should be used tohave the actual floor temperature detected when, for example, the unit is installed close to a wall.Actual procedure to use the settingAlthough the standard setting is normally used with no problem, the setting should be changed in the following cases:(12) Optional Accessories Output SelectionUsing this setting, "operation output signal" and "abnormal output signal" can be provided. Output signal is outputbetween terminals X1 and X2 of "adaptor for wiring", an optional accessory.(13) External ON/OFF InputThis input is used for "ON/OFF operation" and "Protection device input" from the outside. The input is performedfrom the T1-T2 terminal of the operation terminal block in the el. compo. box.Mode No. First Code No. Second CodeNo. Contents11 (21) 901 –4°C (–7.2°F)02 –2°C (–3.6°F)03 0°C (0°F)04 2°C (3.6°F)Environment Operation Mode Problem Setting Value· The unit is installed close to a wall or a window.· High thermal capacity of the floor whose material isconcrete, etc.· There are many heat sources like a PC.· There is a non-negligible heat source such as floorheating.HeatingHeated too much 2°C(3.6°F)Heated little –2°C or –4°C(–3.6°F or –7.2°F)Mode No. First Code No. Second CodeNo. Contents12 (22) 001 Indoor unit thermostat ON/OFF signal is provided.02 —03 Output linked with "Start/Stop" of remote controller is provided.04 In case of "Error Display" appears on the remote controller, outputis provided.05 —06 —07 Only for FXMQ-PBEconomizer (field supply) ON/OFF signal is provided.F2 T1 T2Forced OFFInput AMode No. First Code No. Second CodeNo. Contents12 (22) 101 ON: Forced stop (prohibition of using the remote controller)OFF: Permission of using the remote controller02 OFF → ON: Permission of operationON → OFF: Stop03ON: OperationOFF: The system stops, then the applicable unit indicates A0. Theother indoor units indicate U9.04 —05 Only for FXMQ-PBON: Economizer (field supply) is connected.OFF: Not connected