8.6.8 Relay OutputRelay 1• Terminal 01: common• Terminal 02: normal open 240 V AC• Terminal 03: normal closed 240 V ACRelay 2 (Not AutomationDrive FC 301)• Terminal 04: common• Terminal 05: normal open 400 V AC• Terminal 06: normal closed 240 V ACRelay 1 and relay 2 are programmed in par. 5-40Function Relay,par. 5-41On Delay, Relay, and par. 5-42Off Delay, Relay.Additional relay outputs by using option module MCB 105.8.6.9 Brake Resistor Temperature SwitchFrame size D-E-FTorque: 0.5-0.6 Nm (5 in-lbs)Screw size: M3This input can be used to monitor the temperature of an externally connected brake resistor. If the input between 104 and 106 is established, thefrequency converter will trip on warning / alarm 27, “Brake IGBT”. If the connection is closed between 104 and 105, the frequency converter will trip onwarning / alarm 27, “Brake IGBT”.Normally closed: 104-106 (factory installed jumper)Normally open: 104-105Terminal No. Function106, 104, 105 Brake resistor temperature switch.If the temperature of the brake resistor gets too highand the thermal switch drops out, the frequency con-verter will stop braking. The motor will start coasting.A KLIXON switch must be installed that is `normallyclosed'. If this function is not used, 106 and 104 mustbe short-circuited together.FC 300 Design Guide 8 Electrical InstallationMG.33.BC.02 - VLT® is a registered Danfoss trademark 1858